Modeling of acoustic lined duct with and without grazing air flow by an analytical method
An analytical method is proposed to characterize the sound acoustic transmission in a rectangular lined duct with and without grazing air flow. The acoustic wave number in the duct is determined using Taylor series expansion. The proposed method is validated by comparison with a finite
element method in grazing air flow environment and experimental measurements at grazing sound incidence for the case with no flow. Excellent agreement is found in both configurations. The proposed method is used for sensitivity analysis of acoustic duct lined with micro perforated panel absorber
in order to evaluate the impacts of the inputs parameters on the transmission loss of the duct. It is shown for a constant sound pressure level that the transmission loss of the duct is very sensitive to the cavity depth of the absorber while the resonance of the transmission at high sound
pressure level is controlled by the perforation ratio of the panel. The effects of the perforation diameter and the plate thickness are negligible for higher pressure excitation and the impact of the sound pressure level on the transmission is preponderant.
Document Type: Research Article
Affiliations: GAUS, Department of Mechanical Engineering, Université de Sherbrooke
Publication date: 01 July 2018
NCEJ is the pre-eminent academic journal of noise control. It is the Journal of the Institute of Noise Control Engineering of the USA. Since 1973 NCEJ has served as the primary source for noise control researchers, students, and consultants.
- Information for Authors
- Submit a Paper
- Subscribe to this Title
- Membership Information
- INCE Subject Classification
- Ingenta Connect is not responsible for the content or availability of external websites
- Access Key
- Free content
- Partial Free content
- New content
- Open access content
- Partial Open access content
- Subscribed content
- Partial Subscribed content
- Free trial content