Assessing challenges due to HVAC design constraints and their effects on VAV terminal unit noise - lessons learned from recent projects
For most projects requiring HVAC noise analysis, designers can reliably account for projected noise contributions from VAV terminal units. However, the authors' recent experiences on projects with challenging constraints (e.g., renovations to existing HVAC systems, prohibition of duct
liner and/or flex duct, and restriction to packless/no-media silencers), show that manufacturers' published data are not always sufficient. In the provided project examples, published noise levels for terminal units have required greater consideration because of complexities of the HVAC systems
and building conditions. A variety of contributing factors are discussed, as well as the challenges of in-field testing, diagnostics, and troubleshooting. Key takeaways include the need for coordinating with mechanical engineers about the accuracy of system set points; improving assumptions
made about system pressure drops and manufacturers' data; and identifying project types that require greater consideration when using manufacturers' data.
Document Type: Research Article
Affiliations: K2, a Salas O'Brien company
Publication date: 25 May 2023
The Noise-Con conference proceedings are sponsored by INCE/USA and the Inter-Noise proceedings by I-INCE. NOVEM (Noise and Vibration Emerging Methods) conference proceedings are included. All NoiseCon Proceedings one year or older are free to download. InterNoise proceedings from outside the USA older than 10 years are free to download. Others are free to INCE/USA members and member societies of I-INCE.
- Membership Information
- INCE Subject Classification
- Ingenta Connect is not responsible for the content or availability of external websites
- Access Key
- Free content
- Partial Free content
- New content
- Open access content
- Partial Open access content
- Subscribed content
- Partial Subscribed content
- Free trial content