Acoustic Results of Application of Large Diameter Flexible Piping Connections on High Pressure Centrifugal Pumps
This paper discusses a brief case study related to a high rise building mechanical system. Sound sensitive spaces on floors above and below a mid-level mechanical room were plagued by high levels of tonal noise caused by the operation of a pair of large, high-pressure centrifugal pumps.
Due to the operating pressure, large size, and chemical composition of the circulating fluid, elastomeric flex piping connections were initially omitted from the installation, and braided steel connectors were provided instead. The pumps are vibration isolated on concrete inertia bases, and
all connected piping and conduit are isolated on spring and neoprene hangers. Upon startup of the pumps, high levels of airborne sound in the mechanical room were audible and disturbing to occupants in spaces above and below. After some investigation, custom elastomeric flexible connectors
were sourced and installed on the pumps, resulting in significantly reduced sound transmission to neighboring spaces. In this paper, we present before and after data for airborne noise and slab vibration for this installation.
Document Type: Research Article
Affiliations: Acentech
Publication date: 12 October 2020
The Noise-Con conference proceedings are sponsored by INCE/USA and the Inter-Noise proceedings by I-INCE. NOVEM (Noise and Vibration Emerging Methods) conference proceedings are included. All NoiseCon Proceedings one year or older are free to download. InterNoise proceedings from outside the USA older than 10 years are free to download. Others are free to INCE/USA members and member societies of I-INCE.
- Membership Information
- INCE Subject Classification
- Ingenta Connect is not responsible for the content or availability of external websites
- Access Key
- Free content
- Partial Free content
- New content
- Open access content
- Partial Open access content
- Subscribed content
- Partial Subscribed content
- Free trial content