Evaluation of Receiving Room Diffusivity and the Effect on Low Frequency Impact Insulation Class
The impact insulation class (IIC) test standard is widely used in the building noise control community. This method is governed by ASTM E989 and ASTM E492. Low frequency response (100 Hz - 200 Hz third octave bands) of the floor-ceiling structure is often the limiting factor in IIC
determination. The recorded sound pressure level in the reverberant receiving room in these third octave bands is highly sensitive to diffusion in the room. This means that microphone placement and volumetric averaging are crucial to calculating an accurate IIC value. In this paper, room diffusion
is examined numerically and experimentally in the low frequency IIC third octave bands. It is shown that even for large receiving rooms, the diffuse field assumption may not be valid in these bands if small volume sampling is used. The effects of poor diffusion and/or volumetric averaging
on IIC values is discussed.
Document Type: Research Article
Affiliations: 1: Michigan Technological University 2: GrassWorx, LLC
Publication date: 18 December 2018
The Noise-Con conference proceedings are sponsored by INCE/USA and the Inter-Noise proceedings by I-INCE. NOVEM (Noise and Vibration Emerging Methods) conference proceedings are included. All NoiseCon Proceedings one year or older are free to download. InterNoise proceedings from outside the USA older than 10 years are free to download. Others are free to INCE/USA members and member societies of I-INCE.
- Membership Information
- INCE Subject Classification
- Ingenta Connect is not responsible for the content or availability of external websites
- Access Key
- Free content
- Partial Free content
- New content
- Open access content
- Partial Open access content
- Subscribed content
- Partial Subscribed content
- Free trial content