@article {Cai:2018:0736-2935:6109, title = "Simulationof Transformer Noise Controlling Based on an Equivalent Sound Source Model", journal = "INTER-NOISE and NOISE-CON Congress and Conference Proceedings", parent_itemid = "infobike://ince/incecp", publishercode ="ince", year = "2018", volume = "258", number = "1", publication date ="2018-12-18T00:00:00", pages = "6109-6116", itemtype = "ARTICLE", issn = "0736-2935", url = "https://ince.publisher.ingentaconnect.com/content/ince/incecp/2018/00000258/00000001/art00014", author = "Cai, Xuan and Zhan, Xuelei and Wei, Na and Cai, Yong and Li, Dakun", abstract = "It is very important to study the acoustic radiation model of transformer for the noise radiation prediction in substation.. In this paper, a 110kv outdoor substation with noise barriers was studied, and the Sound Pressure Level(SPL) and frequency spectrum about transformer noise barrier were measured abundantly. Utilizing equivalent source method, each surface of the transformer is equivalent to 9 point sound sources to build a multipoint equivalent acoustic model. This model is established by employing the LMS virtual.lab software, and also the sound radiation is calculated based on the sound line method. A reasonable number of equivalent sound sources is determined by comparing the simulations and the measured values, and the most difference are within 1.5dB between the simulation value and the measured one . It is proved that the equivalent source method of the transformer is applicable to the outdoor substation with sound barriers for forecasting noise radiation.", }